HVAC & TAB Glossary
Clear definitions of common terms used in air balancing, TAB, ventilation, and HVAC performance — organized alphabetically.
- ACH (Air Changes per Hour) (ACH)
- The number of times per hour that the total air volume of a space is supplied by the HVAC system. Calculated as (CFM × 60) ÷ room volume in cubic feet.
- Air Handling Unit (AHU)
- The central mechanical unit that conditions and distributes air — typically containing a fan, heating/cooling coils, a filter section, and dampers.
- Balometer (Flow Hood)
- An instrument that captures airflow at a supply, return, or exhaust outlet and directly measures the volumetric flow rate in CFM.
- CFM (Cubic Feet per Minute) (CFM)
- The standard US unit of volumetric airflow. Design CFM values are assigned to each supply and return outlet by the mechanical engineer.
- Damper
- An adjustable plate inside a duct that restricts or allows airflow. Balancing dampers are used by TAB technicians to proportion airflow; control dampers open and close based on zone demand.
- Design Intent
- The mechanical engineer's documented objectives for an HVAC system — what conditions (temperature, humidity, airflow, pressure) each space should maintain.
- DCV (Demand-Controlled Ventilation) (DCV)
- An HVAC control strategy that modulates outdoor air intake based on measured occupancy (typically using CO₂ sensors), saving energy when spaces are not fully occupied.
- EER / IEER
- Energy Efficiency Ratio and Integrated EER — measures of cooling equipment efficiency. Higher values indicate greater efficiency. IEER accounts for part-load operation.
- External Static Pressure (ESP)
- The total resistance to airflow from all ductwork, coils, filters, dampers, and terminal devices — everything outside the fan housing. Measured in inches of water gauge (in. w.g.).
- Fan Curve
- A graph showing a fan's performance (CFM vs. static pressure) across its operating range. The intersection of the fan curve and the system resistance curve determines the actual operating point.
- HEPA Filter
- High-Efficiency Particulate Air filter — removes ≥99.97% of particles ≥0.3 µm. Required in cleanrooms, operating rooms, and isolation rooms. MERV 17 equivalent.
- Hydronic System
- An HVAC system that uses water (chilled water, hot water, or condenser water) to transfer heating or cooling energy. TAB includes balancing these water flows alongside air flows.
- in. w.g. (Inches of Water Gauge) (in. w.g.)
- The standard unit for measuring HVAC static pressures. 1 in. w.g. = 249 Pa. Typical residential systems have 0.3–0.8 in. w.g. external static pressure.
- ISO 14644
- The international standard defining cleanroom classifications by airborne particle count (ISO classes 1–9) and specifying test methods for cleanroom performance verification.
- Manometer
- An instrument that measures pressure or pressure differential. Used in TAB to measure duct static pressure, filter pressure drop, fan performance, and room-to-room pressure relationships.
- MERV (Minimum Efficiency Reporting Value) (MERV)
- A filter efficiency rating per ASHRAE 52.2. Ranges from MERV 1 (coarse) to MERV 16 (hospital-grade). HEPA filters are rated MERV 17–20.
- NEBB
- National Environmental Balancing Bureau — a certification organization for TAB firms and technicians. Publishes procedural standards for TAB, sound testing, and commissioning.
- AABC
- Associated Air Balance Council — a certification organization for independent TAB agencies. Publishes National Standards for TAB and emphasizes third-party independence.
- Pitot Tube
- A probe that measures velocity pressure (the difference between total pressure and static pressure) in a duct. Combined with a manometer, used to calculate air velocity and perform duct traverses.
- Proportional Balancing
- A systematic TAB method where outlets are adjusted proportionally toward the outlet with the lowest measured/design ratio, ensuring balanced distribution without starving any branch.
- RH (Relative Humidity) (RH)
- The amount of moisture in the air as a percentage of the maximum moisture air can hold at that temperature. ASHRAE recommends maintaining 30–60% RH in occupied spaces.
- Static Pressure
- The pressure of air acting perpendicular to flow — the resistance force in a duct system. Higher static pressure means the fan must work harder to move the same airflow.
- TAB (TAB)
- Testing, Adjusting, and Balancing — the process of measuring, adjusting, and documenting HVAC system performance to verify compliance with design specifications.
- Tachometer
- An instrument that measures rotational speed (RPM) of fans and pumps. Used in TAB to verify fan speed and calculate sheave adjustments for proper airflow.
- Total Static Pressure
- The sum of static pressure and velocity pressure at a point in a duct. Used in fan performance calculations.
- VAV Box (VAV)
- Variable Air Volume terminal device that modulates airflow to a zone based on thermostat demand. Contains an airflow sensor and damper actuator. TAB sets minimum and maximum airflow setpoints.
- VFD (Variable Frequency Drive) (VFD)
- An electronic controller that varies fan or pump motor speed by adjusting the electrical frequency supplied to the motor. Allows precise airflow control and significant energy savings at part load.
- Ventilation Rate Procedure (VRP)
- The primary calculation method in ASHRAE 62.1 for determining outdoor air requirements — combining a per-person rate and a per-floor-area rate for each space type.
Missing a term? These definitions cover the concepts most relevant to air balancing and TAB work. For manufacturer-specific terminology or code-specific definitions, refer to the relevant standard.