5 min read
Air Balance Report Template
An air balance report is the primary deliverable of a Testing, Adjusting, and Balancing (TAB) inspection. It documents the design airflow requirements for each terminal device in a building and records the actual measured airflow โ confirming whether the system is delivering air as the mechanical design specifies.
๐ Educational reference
What Is an Air Balance Report?
A TAB agent visits a building after HVAC installation is complete, measures the actual airflow at each supply diffuser, return grille, and exhaust register, then adjusts dampers and equipment to bring airflow into alignment with the mechanical design. The air balance report captures this process in tabular form.
The report typically includes:
- A system summary for each air handling unit (AHU) or rooftop unit (RTU)
- A line item for every measured terminal device (diffuser, grille, register)
- The design CFM for each device (from the mechanical drawings)
- The final measured CFM after adjustment
- The variance between design and measured airflow
- The TAB agent's certification signature and date
Report Table Structure
The core of an air balance report is a tabular summary of terminal devices. The columns below represent the standard fields found in most TAB reports.
| Room / Area | System | Design CFM | Measured CFM | Difference | Variance % | Notes |
|---|---|---|---|---|---|---|
| Room or space label | AHU or RTU ID | From drawings | Field reading | Measured โ Design | (Diff รท Design) ร 100 | Observations |
Field Explanations
- Room / Area
- The name or number of the room or zone where the terminal device is located. This typically matches the room labels on the mechanical drawings (e.g., "Office 101", "Conference B", "Corridor 2").
- System
- The air handling unit, rooftop unit, or fan coil unit that serves this device. Useful when a building has multiple systems (e.g., "AHU-1", "RTU-3", "FCU-B4").
- Design CFM
- The airflow (in cubic feet per minute) specified by the mechanical engineer in the construction documents. This is the target โ the amount of conditioned air this device is supposed to deliver. Source: mechanical drawings and airflow schedules.
- Measured CFM
- The actual airflow measured in the field by the TAB technician after adjustment. Measured using a flow hood (capture hood), pitot tube traverse, or other approved method per the applicable TAB standard.
- Difference
- The arithmetic difference between measured and design CFM. Calculated as: Measured CFM โ Design CFM. A positive value indicates the device is delivering more than specified; negative means less.
- Variance %
- The percentage deviation from design. Calculated as: (Difference รท Design CFM) ร 100. A commonly referenced tolerance in TAB standards is ยฑ10%, meaning the measured flow should fall within 10% of the design value โ but acceptable variance depends on project specifications and the applicable standard. Check project documents.
- Notes
- Free-text field for observations. Common entries include damper position, device condition, obstructions, ceiling tile status, duct issues noted, or items requiring follow-up.
Example Completed Row
The following is a sample completed row showing how measured results would be recorded for a single supply diffuser.
| Room / Area | System | Design CFM | Measured CFM | Difference | Variance % | Notes |
|---|---|---|---|---|---|---|
| Conference Room A | AHU-2 | 400 | 388 | โ12 | โ3.0% | Damper adjusted. Within tolerance. |
| Office 204 | AHU-2 | 150 | 128 | โ22 | โ14.7% | Ceiling tile obstructing diffuser. Flagged for correction. |
In the second row, the measured CFM is outside the commonly referenced ยฑ10% tolerance band. The TAB technician has flagged this for correction (ceiling tile obstruction) before the report is finalized. Specific acceptance criteria depend on the project specifications โ always verify with the applicable contract documents.
Use the CFM Variance Calculator to quickly compute difference and variance percentage for any device.
โ Not a certified report
Related Guides
CFM Variance Calculator
Calculate the difference and variance % between design and measured CFM
Air Balancing Explained
How the TAB process works and what it measures
TAB Explained
Testing, Adjusting, and Balancing โ the full process
Air Balancing Readiness Checklist
Preparing a building for air balancing