ACH to CFM Calculator
Convert between air changes per hour (ACH) and supply airflow (CFM) in either direction — measured CFM to ACH, or a target ACH to the CFM needed to achieve it. Used in ventilation design, IAQ assessment, and cleanroom specification.
Air Changes per Hour Calculator
Formula: ACH = (CFM × 60) ÷ Room Volume (ft³)
Reference ACH Targets
Understanding ACH
Air changes per hour (ACH) is a measure of how many times the total air volume of a room is supplied — or exhausted — per hour. It is calculated as:
ACH = (Supply CFM × 60) ÷ Room Volume (ft³)
where the multiplication by 60 converts CFM (cubic feet per minute) to cubic feet per hour.
What Does ACH Tell You?
ACH is a useful metric for comparing ventilation rates across differently-sized rooms. A 400 CFM supply delivering 4 ACH to a small office is very different from 4 ACH in a large warehouse — the same number, but very different air volumes and purposes.
In practice, ACH is used alongside ASHRAE standards to verify that a space is receiving adequate ventilation for its occupancy type. Higher-occupancy and higher-risk spaces (operating rooms, isolation rooms, labs) require higher ACH minimums.
Converting ACH to CFM (Reverse Calculation)
Often the requirement comes first: a code, standard, or specification calls for a target ACH, and you need to know what supply airflow achieves it. Rearranging the same formula gives:
CFM = (Target ACH × Room Volume (ft³)) ÷ 60
Example: a hospital patient room measuring 12 ft × 14 ft with a 9 ft ceiling has a volume of 1,512 ft³. ASHRAE 170 requires a minimum of 6 ACH for general patient rooms. Required CFM = (6 × 1,512) ÷ 60 = 151.2 CFM. Use the "ACH → CFM" mode above to run this calculation for your own room dimensions.
ACH vs. Ventilation Rate
ACH is related to, but distinct from, ventilation rate. ASHRAE 62.1 specifies ventilation rates in CFM per person and CFM per ft² of floor area — not directly in ACH. ACH is most commonly specified in healthcare (ASHRAE Standard 170) and cleanroom (ISO 14644) contexts.
Limitations
ACH tells you total air volume replaced, not how effectively that air mixes with the room air or reaches occupant breathing zones. A room with 10 ACH delivered through a single poorly-placed diffuser may have worse contaminant dilution than a room with 6 ACH from well-designed distribution. Air distribution effectiveness (E_v) is the metric that captures mixing quality.
Embed this calculator on your siteFree for contractors, schools, and engineering firms. Copy one snippet; it resizes itself.+
Please keep the credit line under the calculator. The tool runs entirely in your visitors' browsers; nothing they enter is sent anywhere.