Duct Size Calculator

Find the duct size for a given airflow. Enter CFM and either a friction rate or a target velocity. The calculator returns the round duct diameter, the next standard size, and a set of rectangular ducts that carry the same air at the same pressure loss.

📝 Educational estimate

This works like a duct sizing slide rule for straight sheet metal duct. It does not account for fittings, flexible duct, or available fan pressure, and it is not a substitute for a duct design.

Duct Size Calculator

How Duct Sizing Works

Air moving through a duct loses pressure to friction against the duct wall. For a given airflow, a smaller duct means higher velocity and more pressure loss per foot. A larger duct means lower velocity and less loss, at a higher material cost. Sizing a duct is choosing the point on that trade-off.

The equal-friction method fixes the pressure loss per 100 feet and solves for the diameter that produces it. Every section of the system is sized to the same friction rate, so pressure drops evenly along the run and branch dampers have less work to do. This is the method behind a duct sizing slide rule, and it is what this calculator does in the first tab.

Choosing a Friction Rate

The friction rate is not arbitrary. It follows from how much static pressure the fan has left for the ductwork after the coil, filter, and grilles have taken their share, divided by the effective length of the longest run including fittings. A system with little pressure to spare needs a low friction rate and therefore larger ducts.

Velocity Limits

Friction is one limit. Noise is another. Air moving too fast through branch ducts and runouts near occupied rooms is audible at the diffuser. Common practice keeps branch ducts serving quiet spaces well under 1,000 FPM and lets main trunks run faster, since they are farther from the room and often lined. The calculator reports velocity at the selected size so both limits can be checked together.

Round and Rectangular Sizes

Friction data is published for round duct. A rectangular duct is matched to it through the equivalent diameter, the round size with the same pressure loss at the same airflow: De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25, with both sides in inches. A 20 × 8 duct has an equivalent diameter of about 13.5 inches, even though its area is closer to that of a 14.3-inch round duct. The rectangular options listed are the smallest standard sizes that meet the requirement at each height.

Checking an Existing Duct

Sizing in reverse is a useful diagnostic. If a branch is short of air with its damper fully open, compare the duct that was installed with the size this calculator returns for the design airflow. A duct one or two sizes small, or a long flex runout where metal was drawn, explains a shortfall that no amount of damper adjustment will fix. The Duct Friction Loss Calculator estimates the pressure loss of the duct as built.

Embed this calculator on your siteFree for contractors, schools, and engineering firms. Copy one snippet; it resizes itself.+
Preview the embed

Please keep the credit line under the calculator. The tool runs entirely in your visitors' browsers; nothing they enter is sent anywhere.

Frequently Asked Questions

What friction rate should I use to size ductwork?+
Low-velocity commercial and residential supply duct is commonly sized at about 0.08 to 0.10 in. w.g. per 100 ft, and return duct somewhat lower, often around 0.05 to 0.08. The right value for a specific system comes from the pressure the fan has available divided by the total effective length of the longest duct run, which is how residential Manual D and commercial equal-friction design arrive at it. A lower friction rate gives larger, quieter duct that costs more to install.
What size duct do I need for 1,000 CFM?+
At a friction rate of 0.08 in. w.g. per 100 ft, 1,000 CFM calculates to about 14.5 inches round, so a 16-inch round duct, or a rectangular duct such as 20 × 10 or 16 × 12. At 0.10 the calculated size drops to roughly 13.9 inches and a 14-inch round duct works. Enter your own airflow and friction rate above for other cases.
Why is the rectangular duct bigger in area than the round duct?+
A rectangular duct has more wall surface for the same cross-sectional area, so it produces more friction. To carry the same airflow at the same pressure loss it needs more area than the round duct it replaces. The flatter the rectangle, the larger the penalty, which is why this calculator stops at a 4:1 aspect ratio.
Should I size by friction rate or by velocity?+
Friction rate is the usual method for supply and return duct in comfort systems because it keeps pressure loss per foot roughly constant along the run. Velocity sizing is used where air speed is the controlling limit: exhaust systems that must keep dust or grease in suspension, runouts near quiet rooms where noise matters, and transfer ducts.
Does this work for flex duct?+
Not directly. Flexible duct has much higher friction than sheet metal, and the loss rises sharply when it is not pulled tight. A common field practice is to go up one size from the metal duct result for a fully stretched flex run, but the manufacturer's friction data should govern.