Velocity Pressure Calculator
Convert a pitot tube velocity pressure reading to air velocity and CFM, convert the other way, or paste in a whole duct traverse and get the average velocity and airflow with the averaging done correctly.
📝 Educational use
Velocity Pressure Calculator
What Velocity Pressure Is
Moving air exerts two kinds of pressure. Static pressure pushes outward on the duct wall in every direction, whether the air is moving or not. Velocity pressure exists only because the air is moving, and acts in the direction of flow. Their sum is total pressure.
A pitot tube senses total pressure at its tip and static pressure through small holes around its side. Connect the two ports to opposite sides of a manometer and the instrument subtracts one from the other, leaving velocity pressure. From that single number the air speed follows:
V = 4005 × √VP for standard air, or V = 1096.7 × √(VP ÷ density) in general.
Reference Values at Standard Air
| Velocity pressure (in. w.g.) | Velocity (FPM) |
|---|---|
| 0.01 | 400 |
| 0.02 | 566 |
| 0.04 | 801 |
| 0.0625 | 1,001 |
| 0.10 | 1,266 |
| 0.25 | 2,003 |
| 0.50 | 2,832 |
| 1.00 | 4,005 |
The table shows why low velocities are hard to measure with a pitot tube. Halving the velocity cuts the pressure signal to a quarter. At 400 FPM there is only a hundredth of an inch of water to read.
From Velocity to CFM
Airflow is average velocity multiplied by the cross-sectional area of the duct in square feet: CFM = V × A. Use the inside dimensions. On lined duct, subtract the liner thickness from each side, since a one-inch liner takes two inches off both the width and the height.
A single centerline reading is not the average. Velocity is highest near the middle of the duct and falls toward the walls, so airflow is calculated from a traverse: a grid of readings that each represent an equal share of the area.
Reducing a Traverse
The Traverse readings tab takes the full list of velocity pressures, converts each one to velocity, and averages the velocities. It also reports two checks:
- The effect of averaging pressures first. This is the most common arithmetic mistake in traverse work, and the calculator shows how far off it would have put the answer.
- The share of readings above one tenth of the maximum. A widely used rule for judging a traverse location is that at least 75% of the velocity pressure readings should exceed 10% of the highest reading. When they do not, the profile is too uneven and the location should be moved.
Embed this calculator on your siteFree for contractors, schools, and engineering firms. Copy one snippet; it resizes itself.+
Please keep the credit line under the calculator. The tool runs entirely in your visitors' browsers; nothing they enter is sent anywhere.
Frequently Asked Questions
What is the formula for velocity pressure to FPM?+
Where does the 4005 constant come from?+
Why can't I average the velocity pressures and convert once?+
What is the lowest velocity a pitot tube can measure?+
When does air density matter?+
Related Tools & Topics
How to Do a Pitot Tube Traverse
Choosing the location, laying out points, and reducing the readings
Duct Traverse Point Planner
Measurement point positions for a round duct
Air Density Correction Calculator
Air density from altitude and temperature
Air Balancing Equipment and Tools
Pitot tubes, manometers, hoods, and anemometers compared