Velocity Pressure Calculator

What Velocity Pressure Is

Moving air exerts two kinds of pressure. Static pressure pushes outward on the duct wall in every direction, whether the air is moving or not. Velocity pressure exists only because the air is moving, and acts in the direction of flow. Their sum is total pressure.

A pitot tube senses total pressure at its tip and static pressure through small holes around its side. Connect the two ports to opposite sides of a manometer and the instrument subtracts one from the other, leaving velocity pressure. From that single number the air speed follows:

V = 4005 × √VP for standard air, or V = 1096.7 × √(VP ÷ density) in general.

Reference Values at Standard Air

Velocity pressure (in. w.g.) Velocity (FPM)
0.01 400
0.02 566
0.04 801
0.0625 1,001
0.10 1,266
0.25 2,003
0.50 2,832
1.00 4,005

The table shows why low velocities are hard to measure with a pitot tube. Halving the velocity cuts the pressure signal to a quarter. At 400 FPM there is only a hundredth of an inch of water to read.

From Velocity to CFM

Airflow is average velocity multiplied by the cross-sectional area of the duct in square feet: CFM = V × A. Use the inside dimensions. On lined duct, subtract the liner thickness from each side, since a one-inch liner takes two inches off both the width and the height.

A single centerline reading is not the average. Velocity is highest near the middle of the duct and falls toward the walls, so airflow is calculated from a traverse: a grid of readings that each represent an equal share of the area.

Reducing a Traverse

The Traverse readings tab takes the full list of velocity pressures, converts each one to velocity, and averages the velocities. It also reports two checks:

Embed this calculator on your siteFree for contractors, schools, and engineering firms. Copy one snippet; it resizes itself.+
Preview the embed

Please keep the credit line under the calculator. The tool runs entirely in your visitors' browsers; nothing they enter is sent anywhere.

Frequently Asked Questions

What is the formula for velocity pressure to FPM?+
For standard air, V = 4005 × √VP, where V is velocity in feet per minute and VP is velocity pressure in inches of water gauge. A reading of 0.0625 in. w.g. is 4005 × 0.25 = about 1,000 FPM. For air that is not at standard density the full form is V = 1096.7 × √(VP ÷ density), with density in pounds per cubic foot.
Where does the 4005 constant come from?+
It is the general constant 1096.7 divided by the square root of standard air density, 0.075 lb/ft³. The square root of 0.075 is about 0.2739, and 1096.7 ÷ 0.2739 is about 4005. The constant bundles the unit conversions between inches of water, pounds per cubic foot, and feet per minute.
Why can't I average the velocity pressures and convert once?+
Because velocity depends on the square root of velocity pressure, and the square root of an average is not the average of the square roots. Averaging the pressures first always gives a result that is too high. On a reasonably flat velocity profile the error is small, but on an uneven profile it can reach several percent. Convert each reading to velocity, then average the velocities.
What is the lowest velocity a pitot tube can measure?+
The limit is set by the manometer, not the tube. At 400 FPM the velocity pressure is only 0.01 in. w.g., which is at the edge of what many field instruments resolve reliably. Pitot traverses are generally trusted above roughly 600 to 700 FPM. Below that, a thermal anemometer or another method is the better choice.
When does air density matter?+
Whenever the air is far from 70°F at sea level. At 5,000 ft elevation, air density is about 17% lower than standard, and the same velocity pressure corresponds to roughly 9 to 10% higher actual velocity. Hot exhaust and high-altitude sites are the common cases. Use the Air Density Correction Calculator to find the density, then enter it here.