VAV K-Factor Calculator
A K-factor turns the pressure signal from a flow sensor into CFM. Use this calculator to find a K-factor from a field measurement, to find the airflow a given K-factor and pressure represent, or to correct the K-factor in a VAV controller so its reading matches what you measured.
📝 Educational use
VAV K-Factor Calculator
What a K-Factor Is
A VAV terminal unit measures its own airflow. A multi-point sensor at the box inlet picks up total pressure on one set of ports and a lower pressure on another, and the difference between them is piped to a transducer in the controller. That differential pressure rises with the square of the airflow, so airflow is recovered by taking a square root and multiplying by a constant:
CFM = K × √ΔP
K is the airflow through that box when the sensor signal is exactly 1.0 in. w.g. It depends on the inlet size and the sensor design. An 8-inch inlet will have a K somewhere in the high hundreds or low thousands depending on the manufacturer, and the value for each inlet size is listed in the product data.
The sensor signal is deliberately larger than true velocity pressure. Amplifying it is what lets a controller read low airflows, and it is the reason a box cannot be checked with 4005 × √VP × area using the sensor reading alone.
Other Forms of the Same Constant
Not every controller asks for K. Common alternatives:
- Box area plus a flow coefficient or pickup gain. The controller computes
CFM = 4005 × area × √(ΔP ÷ gain). The gain is the sensor's amplification factor. - A multiplier or calibration factor applied to the calculated flow, with 1.0 meaning no correction.
- CFM at a stated reference pressure other than 1.0 in. w.g.
For K itself and for any straight multiplier, displayed airflow is directly proportional to the constant, so the correction is the simple ratio in the third tab. A gain that sits under the square root works the other way and is not linear: to raise the displayed flow by a given ratio, the gain is divided by that ratio squared. The controller documentation says which form applies.
Correcting a VAV Box in the Field
- Drive the box to its maximum airflow setpoint and let it settle.
- Measure the actual airflow, normally by totaling capture hood readings at every diffuser the box serves, or by a duct traverse where the downstream duct allows one.
- Read the airflow the controller displays at the same moment.
- Calculate the corrected constant:
new K = old K × measured ÷ displayed. - Enter it, let the box re-control to setpoint, and measure again to confirm.
- Check the reading at minimum airflow.
Duct leakage between the box and the diffusers makes the hood total lower than the true box airflow. On leaky downstream duct, correcting to the hood total builds that leakage into the calibration. Where the difference is large, the leakage is the finding to report.
K-Factor Is Not Ak Factor
The two are easy to confuse because both are manufacturer constants used to get CFM. A K-factor works on a pressure signal with a square root. An Ak factor is an effective area that multiplies a face velocity measured at a grille or diffuser: CFM = velocity × Ak. One belongs to flow sensors, the other to air outlets.
Embed this calculator on your siteFree for contractors, schools, and engineering firms. Copy one snippet; it resizes itself.+
Please keep the credit line under the calculator. The tool runs entirely in your visitors' browsers; nothing they enter is sent anywhere.
Frequently Asked Questions
What is a K-factor in HVAC?+
What is the difference between K-factor and Ak factor?+
Why does the K-factor need correcting if the manufacturer publishes it?+
How do I calculate a new K-factor?+
At what airflow should a VAV box be calibrated?+
Related Tools & Topics
Ak Factor Register Airflow Estimator
Airflow at a grille from face velocity and Ak factor
Commercial Air Balancing
How VAV and constant volume systems are balanced
TAB Procedure: Step by Step
The full balancing sequence, including VAV calibration
Velocity Pressure Calculator
Convert pressure readings to velocity and CFM