VAV K-Factor Calculator

A K-factor turns the pressure signal from a flow sensor into CFM. Use this calculator to find a K-factor from a field measurement, to find the airflow a given K-factor and pressure represent, or to correct the K-factor in a VAV controller so its reading matches what you measured.

📝 Educational use

Controller manufacturers store this constant in different forms and units. Confirm what your controller expects before entering a value, and record both the original and the corrected constant.

VAV K-Factor Calculator

What a K-Factor Is

A VAV terminal unit measures its own airflow. A multi-point sensor at the box inlet picks up total pressure on one set of ports and a lower pressure on another, and the difference between them is piped to a transducer in the controller. That differential pressure rises with the square of the airflow, so airflow is recovered by taking a square root and multiplying by a constant:

CFM = K × √ΔP

K is the airflow through that box when the sensor signal is exactly 1.0 in. w.g. It depends on the inlet size and the sensor design. An 8-inch inlet will have a K somewhere in the high hundreds or low thousands depending on the manufacturer, and the value for each inlet size is listed in the product data.

The sensor signal is deliberately larger than true velocity pressure. Amplifying it is what lets a controller read low airflows, and it is the reason a box cannot be checked with 4005 × √VP × area using the sensor reading alone.

Other Forms of the Same Constant

Not every controller asks for K. Common alternatives:

For K itself and for any straight multiplier, displayed airflow is directly proportional to the constant, so the correction is the simple ratio in the third tab. A gain that sits under the square root works the other way and is not linear: to raise the displayed flow by a given ratio, the gain is divided by that ratio squared. The controller documentation says which form applies.

Correcting a VAV Box in the Field

  1. Drive the box to its maximum airflow setpoint and let it settle.
  2. Measure the actual airflow, normally by totaling capture hood readings at every diffuser the box serves, or by a duct traverse where the downstream duct allows one.
  3. Read the airflow the controller displays at the same moment.
  4. Calculate the corrected constant: new K = old K × measured ÷ displayed.
  5. Enter it, let the box re-control to setpoint, and measure again to confirm.
  6. Check the reading at minimum airflow.

Duct leakage between the box and the diffusers makes the hood total lower than the true box airflow. On leaky downstream duct, correcting to the hood total builds that leakage into the calibration. Where the difference is large, the leakage is the finding to report.

K-Factor Is Not Ak Factor

The two are easy to confuse because both are manufacturer constants used to get CFM. A K-factor works on a pressure signal with a square root. An Ak factor is an effective area that multiplies a face velocity measured at a grille or diffuser: CFM = velocity × Ak. One belongs to flow sensors, the other to air outlets.

Embed this calculator on your siteFree for contractors, schools, and engineering firms. Copy one snippet; it resizes itself.+
Preview the embed

Please keep the credit line under the calculator. The tool runs entirely in your visitors' browsers; nothing they enter is sent anywhere.

Frequently Asked Questions

What is a K-factor in HVAC?+
A K-factor is a constant that converts a pressure reading into airflow: CFM = K × √ΔP. It is published by the manufacturer of a flow-measuring device, most often the flow sensor at the inlet of a VAV terminal unit, and it is numerically equal to the airflow through that device when the sensor reads 1.0 in. w.g. The same idea is used for airflow measuring stations, some diffusers, chilled beams, and fan inlet sensors.
What is the difference between K-factor and Ak factor?+
They are different constants used with different measurements. A K-factor multiplies the square root of a pressure signal to give CFM. An Ak factor is an effective area in square feet that multiplies a face velocity in FPM to give CFM at a grille, register, or diffuser. Both come from the manufacturer, and both are specific to one model and size.
Why does the K-factor need correcting if the manufacturer publishes it?+
The published value assumes laboratory inlet conditions, usually several diameters of straight duct ahead of the sensor. In the field, an elbow, a flex connection, or a reducer close to the box inlet changes the velocity profile at the sensor, and the transducer in the controller has its own tolerance. Measuring actual airflow and adjusting the constant brings the controller's reading into line with reality.
How do I calculate a new K-factor?+
New K = old K × measured CFM ÷ displayed CFM. If the controller shows 900 CFM while a capture hood total at the downstream diffusers reads 820 CFM, and the current K is 1,310, the corrected K is 1,310 × 820 ÷ 900 = about 1,194. After the change, the controller should read 820 CFM at the same damper position.
At what airflow should a VAV box be calibrated?+
Close to maximum design airflow, where the sensor signal is strongest and measurement error is smallest as a percentage. Many balancing procedures then verify the result at minimum airflow. At very low flows the pressure signal from the sensor becomes tiny, so an error at minimum often points to a minimum setpoint that is below what the sensor can read reliably.