Air Balance Report Builder
A fillable air balance report sheet that does the arithmetic for you. Enter the design and measured CFM for each diffuser, grille, or register. The sheet calculates the difference and variance, flags anything outside tolerance, totals supply, return, and exhaust, and exports the result as a PDF or a CSV file.
📝 Working record, not a certified report
Air Balance Report Builder
| Room / Area | Terminal | Type | Design CFM | Measured CFM | Diff. | Variance | Notes | Remove |
|---|---|---|---|---|---|---|---|---|
| — | — | |||||||
| — | — | |||||||
| — | — |
Everything you enter stays in this browser. Nothing is uploaded, and the worksheet is kept on this device so you can come back to it. Variance is (Measured − Design) ÷ Design × 100.
How to Fill In the Sheet
- Header. Record the project, the system the terminals belong to (one sheet per air handler or rooftop unit keeps things readable), the date, who took the readings, and which instrument was used.
- Tolerance. Set the acceptance band from the project specification. The default is ±10%.
- One line per terminal. Enter the room, the terminal tag from the drawings, whether it is supply, return, or exhaust, and the design CFM from the mechanical schedule.
- Measured CFM. Enter the final reading after adjustment. The difference and variance appear as you type.
- Notes. Record anything that explains a reading: a damper found closed, a blocked diffuser, a terminal that could not be reached.
- Export. Print / Save as PDF produces a formatted report page with a signature line. Download CSV gives a file that opens in any spreadsheet.
What the Columns Mean
Design CFM is the airflow the mechanical engineer assigned to that terminal. It comes from the air device schedule or the plan tags on the mechanical drawings.
Measured CFM is the field reading, normally taken with a capture hood at diffusers and grilles, or calculated from a duct traverse where a hood cannot be used.
Difference is measured minus design. A negative number means the terminal is short of air.
Variance expresses that difference as a percentage of design, which is how TAB tolerances are written. Green means within the tolerance you set. Red means outside it.
Reading the Totals
The summary adds up each terminal type. Three comparisons are worth making:
- Total supply against design. If every terminal is a little low, the problem is at the fan, not at the dampers. Fan speed, a loaded filter, or high static pressure is limiting the whole system.
- Total supply against the fan airflow measured by duct traverse. The gap is duct leakage.
- Supply against return plus exhaust. The difference is what pressurizes or depressurizes the space.
When Terminals Fail
A terminal outside tolerance is a finding, not a verdict. Before recording it as a deficiency, a technician checks the obvious causes: the volume damper position, a crushed or disconnected flex duct, a ceiling tile or furniture blocking the device, and whether the system was in its design operating mode when the reading was taken. If the terminal still cannot reach design with its damper fully open, the cause is upstream, and the note should say so.
Embed this calculator on your siteFree for contractors, schools, and engineering firms. Copy one snippet; it resizes itself.+
Please keep the credit line under the calculator. The tool runs entirely in your visitors' browsers; nothing they enter is sent anywhere.
Frequently Asked Questions
Is this a certified air balance report?+
How is variance calculated?+
What tolerance should I use?+
Why does the total supply not equal the fan airflow?+
Where is my data stored?+
Can I use it for return and exhaust air too?+
Related Tools & Topics
How to Read an Air Balance Report