Air Balance Report Builder

A fillable air balance report sheet that does the arithmetic for you. Enter the design and measured CFM for each diffuser, grille, or register. The sheet calculates the difference and variance, flags anything outside tolerance, totals supply, return, and exhaust, and exports the result as a PDF or a CSV file.

📝 Working record, not a certified report

This tool records and checks airflow readings. It does not certify them. Where a project specification calls for a certified TAB report, that report must come from a certified TAB firm.

Air Balance Report Builder

Room / AreaTerminalTypeDesign CFMMeasured CFMDiff.VarianceNotesRemove
——
——
——

Everything you enter stays in this browser. Nothing is uploaded, and the worksheet is kept on this device so you can come back to it. Variance is (Measured − Design) ÷ Design × 100.

How to Fill In the Sheet

  1. Header. Record the project, the system the terminals belong to (one sheet per air handler or rooftop unit keeps things readable), the date, who took the readings, and which instrument was used.
  2. Tolerance. Set the acceptance band from the project specification. The default is ±10%.
  3. One line per terminal. Enter the room, the terminal tag from the drawings, whether it is supply, return, or exhaust, and the design CFM from the mechanical schedule.
  4. Measured CFM. Enter the final reading after adjustment. The difference and variance appear as you type.
  5. Notes. Record anything that explains a reading: a damper found closed, a blocked diffuser, a terminal that could not be reached.
  6. Export. Print / Save as PDF produces a formatted report page with a signature line. Download CSV gives a file that opens in any spreadsheet.

What the Columns Mean

Design CFM is the airflow the mechanical engineer assigned to that terminal. It comes from the air device schedule or the plan tags on the mechanical drawings.

Measured CFM is the field reading, normally taken with a capture hood at diffusers and grilles, or calculated from a duct traverse where a hood cannot be used.

Difference is measured minus design. A negative number means the terminal is short of air.

Variance expresses that difference as a percentage of design, which is how TAB tolerances are written. Green means within the tolerance you set. Red means outside it.

Reading the Totals

The summary adds up each terminal type. Three comparisons are worth making:

When Terminals Fail

A terminal outside tolerance is a finding, not a verdict. Before recording it as a deficiency, a technician checks the obvious causes: the volume damper position, a crushed or disconnected flex duct, a ceiling tile or furniture blocking the device, and whether the system was in its design operating mode when the reading was taken. If the terminal still cannot reach design with its damper fully open, the cause is upstream, and the note should say so.

Embed this calculator on your siteFree for contractors, schools, and engineering firms. Copy one snippet; it resizes itself.+
Preview the embed

Please keep the credit line under the calculator. The tool runs entirely in your visitors' browsers; nothing they enter is sent anywhere.

Frequently Asked Questions

Is this a certified air balance report?+
No. A certified TAB report is issued by a NEBB, AABC, or TABB certified firm, follows that body's procedural standard, lists calibrated instruments, and carries the certified professional's stamp or signature. This builder produces a clean working record of design and measured airflow. It is useful for in-house checks, pre-balance surveys, maintenance records, and training, but it does not replace a certified report where the specification requires one.
How is variance calculated?+
Variance % = (Measured CFM − Design CFM) ÷ Design CFM × 100. A diffuser designed for 400 CFM that measures 388 CFM has a variance of −3.0%. The builder marks a terminal as within tolerance when the absolute variance is at or below the tolerance you set.
What tolerance should I use?+
Use the tolerance in the project specification. ±10% of design is the value most often referenced for individual terminals. Specifications for hospitals, laboratories, and cleanrooms frequently tighten it, and some set a different band for system totals than for individual outlets. If there is no specification, ±10% is a reasonable working default.
Why does the total supply not equal the fan airflow?+
The sum of the outlets is what reaches the rooms. The fan moves that amount plus whatever leaks out of the ductwork between the fan and the terminals. A gap of a few percent is normal. A large gap points to duct leakage, an open access door, a disconnected runout, or a measurement problem, and is worth recording in the notes.
Where is my data stored?+
Only in your browser. Nothing you type is sent to a server. The worksheet is saved in this browser's local storage so it is still there if you close the tab, and the Clear button removes it. Use Print / Save as PDF or Download CSV to keep a copy.
Can I use it for return and exhaust air too?+
Yes. Each line has a type of Supply, Return, or Exhaust, and the summary totals each type separately. Comparing total supply against total return plus exhaust shows whether the area is net positive or net negative.