Duct Traverse Point Planner
Generate the correct velocity measurement point positions for a round duct traverse using the Equal Area Method — the field procedure TAB technicians use to get an accurate average velocity reading instead of a single, misleading center-point measurement.
📝 Educational reference
Duct Traverse Point Planner — Equal Area Method
Why a Single Reading Isn't Enough
Air velocity across a duct's cross-section is never uniform. Friction against the duct wall slows air near the perimeter; the highest velocity sits nearer the center. A velocity probe held at the center of a duct reads the peak of that profile, not the average — using it directly to calculate CFM (velocity × area) systematically overstates actual airflow, sometimes significantly.
A traverse solves this by sampling velocity at multiple points chosen to represent equal shares of the duct's total area, then averaging the readings. That average is a much closer estimate of true average velocity across the whole cross-section.
How the Equal Area Method Works
Picture the duct's circular cross-section divided into concentric rings — like a target — where every ring has exactly the same area, even though the outer rings are thinner (since area grows with the square of radius). If you measured at the center of each ring's width, the readings wouldn't be evenly weighted by area, because the ring boundaries aren't evenly spaced.
Instead, the Equal Area Method places each measurement point at the specific radius that splits its own ring into two smaller rings of equal area. That point, mathematically: r_k = R × √((2k−1) / 2N), where R is the duct radius, N is the number of rings (points per radius), and k is the ring number counting outward from the center. Because every point now represents an equal share of total cross-sectional area, a plain arithmetic average of the velocity readings is a valid estimate of the area-weighted average velocity — no separate weighting calculation needed in the field.
Field Procedure
- Mark the calculated distances on a traverse rod or probe extension, measured from one duct wall.
- Drill or use an existing traverse port at the correct location — ideally at least 7.5 duct diameters downstream and 3 diameters upstream of any elbow, transition, or damper, per standard practice, to measure in reasonably developed flow.
- Insert the probe to each marked distance in turn and record the velocity reading (typically with a pitot tube and manometer, or a thermal/vane anemometer).
- Repeat the full set of readings along a second port, on a diameter line perpendicular to the first.
- Average all readings to get average velocity; multiply by the duct's cross-sectional area to get CFM.
Common Mistakes
Using too few points in a large duct: fewer points means each one represents a larger area, magnifying the effect of local turbulence or measurement error on the average.
Traversing too close to a fitting: disturbed, non-developed flow near an elbow or damper produces a velocity profile the Equal Area Method's assumptions don't hold up well against — relocate the traverse port if at all possible.
Traversing along only one diameter: skips the averaging benefit of a second, perpendicular line and is more sensitive to any asymmetry in the flow.
Embed this calculator on your siteFree for contractors, schools, and engineering firms. Copy one snippet; it resizes itself.+
Please keep the credit line under the calculator. The tool runs entirely in your visitors' browsers; nothing they enter is sent anywhere.
Frequently Asked Questions
What is a duct traverse and why is it necessary?+
What is the Equal Area Method specifically?+
How many traverse points should I use?+
Do I traverse along more than one diameter?+
Does this method work for rectangular ducts?+
Related Tools & Topics
Air Balancing Explained
Instruments and methods used in the TAB process
Duct Friction Loss Calculator
Estimate velocity and static pressure loss for a duct run
CFM Variance Calculator
Check measured airflow against ±10% design tolerance
TAB Explained
The full Testing, Adjusting, and Balancing process
Velocity Pressure Calculator
Reduce traverse readings to average velocity and CFM
How to Do a Pitot Tube Traverse
Location, point layout, readings, and calculation