How to Do a Pitot Tube Traverse

A capture hood tells you what comes out of one diffuser. To know what a fan is delivering, how much outside air a unit is bringing in, or how air divides between two main branches, the airflow has to be measured inside the duct. The pitot tube traverse is the standard way to do that, and it is the measurement the rest of a balance report is checked against.

📝 Educational overview

This guide describes common practice. Traverses for a certified TAB report follow the point counts and procedures of the governing standard (NEBB, AABC, TABB, or ASHRAE 111).

Why a Traverse Is Necessary

Air does not move through a duct at one speed. Friction slows it at the walls, and it runs fastest somewhere near the center. Fittings push the fast region to one side. A single reading at the centerline can be 10 to 20 percent above the true average, and a single reading anywhere else is a guess.

A traverse replaces that guess with a sample. The cross-section is divided into many small areas, velocity is measured in each, and the results are averaged. The more uneven the profile, the more points it takes to capture it.

What You Need

Step 1: Choose the Location

This decision affects accuracy more than anything done afterward. Look for the longest straight section of duct and place the traverse plane toward its downstream end. The usual guideline is 7.5 duct diameters of straight duct before the plane and 3 after it. For rectangular duct, use the equivalent diameter.

Avoid, in rough order of harm: locations just after an elbow, just after a fan discharge, after a partly closed damper, after a branch takeoff, and inside or just after a transition. Where no good location exists, choose the least bad one, increase the number of points, and note the conditions on the data sheet.

Check access before drilling. The tube has to be inserted and withdrawn along its full length, so there must be clear space outside the duct equal to the duct's depth.

Step 2: Measure the Duct

Measure the inside dimensions. On externally insulated duct, that means the sheet metal size. On internally lined duct, subtract twice the liner thickness from both the width and the height. An error here goes straight into the result: recording a lined 24 × 12 duct at its sheet metal size overstates the area, and the CFM, by about 31 percent with one-inch liner.

Area in square feet is width × height ÷ 144 for rectangular duct, and π × diameter² ÷ 4 ÷ 144 for round, with dimensions in inches.

Step 3: Lay Out the Points

Rectangular duct

The equal-area method divides the cross-section into a grid of equal rectangles and takes one reading at the center of each. The rules of thumb are a minimum of 16 points and no more than about 6 inches between adjacent points, up to a practical maximum of 64.

For a 24 × 12 inch duct, a 4 × 4 grid works. Across the 24-inch side the columns are at 3, 9, 15, and 21 inches from one wall. Across the 12-inch side the rows are at 1.5, 4.5, 7.5, and 10.5 inches. Four holes in the side of the duct, one for each row, give access to all 16 points.

The log-Tchebycheff method places points closer to the walls, according to a table, to account for the slower air there. It uses 5 to 7 points per side depending on the dimension, at least 25 in total, and is considered the more accurate of the two.

Round duct

Round ducts are traversed along two diameters at right angles to each other. Points are not evenly spaced. They are placed so that each represents an equal ring of area, which puts them closer together near the wall. The Duct Traverse Point Planner calculates the insertion depths for any diameter.

Mark the tube

Mark each insertion depth on the pitot tube stem with tape or a marker, measured from the center of the tip. With the marks in place, the technician reads depth at the duct wall and does not have to measure during the traverse.

Step 4: Connect and Zero

Connect the total pressure port to the positive side of the manometer and the static port to the negative side. The instrument then reads velocity pressure. Zero the manometer with both hoses connected and the tube out of the airstream. Check the hoses for kinks and the tube for a blocked tip or blocked static holes, which is common after a tube has been through insulation.

Step 5: Take the Readings

  1. Insert the tube to the first mark with the tip pointing directly upstream, parallel to the duct walls. The tip has to face the flow within about 10 degrees. Most tubes have a pointer or a flat on the stem that shows tip direction from outside.
  2. Hold the stem against the edge of the hole to steady it, and seal around it with a hand or a grommet so the hole does not leak during the reading.
  3. Let the reading settle. Most digital manometers have a time-averaging setting that helps with turbulent flow.
  4. Record the velocity pressure and move to the next mark.
  5. If a reading is zero or negative, record it as zero. It means reverse flow or an eddy at that point, which is information about the location.

Also record the static pressure and air temperature at the traverse plane. They go on the data sheet and are needed for density correction.

Step 6: Calculate the Airflow

Convert every velocity pressure to a velocity, then average the velocities:

V = 4005 × √VP for standard air

CFM = average V × area

Do not average the pressures and convert once. Because of the square root, that always overstates the result. On a traverse where readings range evenly from 0.02 to 0.09 in. w.g., the error is about 2 percent, and it grows as the profile gets rougher.

Example: the 16 readings in the 24 × 12 duct convert to velocities that average 1,150 FPM. The duct is unlined, so its area is 24 × 12 ÷ 144 = 2.0 ft². Airflow is 1,150 × 2.0 = 2,300 CFM.

The Velocity Pressure Calculator has a traverse mode that takes the whole list of readings and does this correctly.

Step 7: Check the Quality of the Traverse

A widely used acceptance check: at least 75 percent of the velocity pressure readings should be greater than one tenth of the maximum reading. A traverse that fails it has large dead or reversed zones, and its average is not reliable. Move to another location if there is one. If not, report the result with a note about the profile.

A second check is plain sense. Readings should change gradually from point to point. One wildly different value is more likely a measurement slip than a feature of the airflow, and is worth repeating.

Step 8: Correct for Density Where Needed

The 4005 constant assumes standard air, 0.075 lb/ft³, which is air at about 70°F at sea level. For air between roughly 40°F and 100°F below 1,000 feet elevation the error from ignoring density is small. Beyond that, use the general form V = 1096.7 × √(VP ÷ density). At 5,000 feet elevation the correction is close to 10 percent. Hot exhaust streams need it at any elevation.

Step 9: Seal the Holes

Plug every test hole. An unplugged hole is a small leak, a whistle, and on a lined or insulated duct a path for moisture. Mark the location so the traverse can be repeated at the same plane later.

Common Mistakes

FAQ

What is a pitot tube traverse?+
A pitot tube traverse is a method of measuring airflow in a duct. A pitot tube is inserted through small holes in the duct wall and moved to a planned grid of points across the duct's cross-section. The velocity pressure at each point is converted to velocity, the velocities are averaged, and the average is multiplied by the duct's cross-sectional area to give airflow in CFM.
How many points are needed for a duct traverse?+
It depends on the duct size and the method. For rectangular ducts, the equal-area method uses a minimum of 16 points with no more than about 6 inches between them, and the log-Tchebycheff method uses at least 25. For round ducts, readings are taken along two diameters at right angles, commonly 6 to 10 points on each. The governing TAB standard sets the exact requirement.
Where is the best place to traverse a duct?+
In the longest straight run available, as far downstream from elbows, transitions, dampers, and branch takeoffs as possible. The common guideline is at least 7.5 duct diameters of straight duct upstream of the traverse plane and 3 diameters downstream. Those lengths are often not available in real buildings, and the technician picks the best location there is and checks the quality of the readings.
How accurate is a pitot tube traverse?+
In a good location with a uniform profile, a careful traverse is generally accepted to be within about 5% of true airflow. In a poor location, close to a fitting or with a distorted profile, the error can be 10% or more. This is why the location and the quality check are recorded with the result.
Which port of the pitot tube goes to which side of the manometer?+
The total pressure port, which is in line with the main stem, connects to the high or positive side. The static pressure port, which branches off the side of the stem, connects to the low or negative side. Connected this way the manometer displays velocity pressure directly. If the reading is negative, the hoses are reversed or the tip is pointing downstream.
Can I traverse with an anemometer instead of a pitot tube?+
Yes. A thermal anemometer probe can be traversed over the same grid of points, and it is the better choice when duct velocity is below roughly 600 FPM, where a pitot tube's pressure signal is too small. The readings are already in FPM, so they are averaged directly.