Title 24 Airflow and Fan Efficacy Checker

Enter a system's tonnage, measured airflow, and fan power to check it against the mandatory airflow and fan efficacy limits for single-family homes in California's 2025 Energy Code.

📝 Pre-test check

Field verification follows Reference Residential Appendix RA3.3 and is performed by an ECC-Rater. Use this to see whether a system is likely to pass before the visit.

Title 24 Airflow and Fan Efficacy Checker (single-family, 2025 Energy Code)

Minimum 350 CFM per ton · Maximum 0.58 W/CFM

Why These Two Numbers Matter

An air conditioner's rated efficiency assumes design airflow across its coil. Too little air means lower capacity, a colder coil, and in the worst case a frozen one. Fan efficacy measures what it costs to move that air. Together they show whether the duct system lets the equipment perform as rated.

Both depend on the duct system more than on the equipment. Undersized returns, a restrictive filter, or a long flex run reduce airflow and drive up fan power at the same time, which is why systems tend to fail both tests together and why fixing the ducts fixes both.

Embed this calculator on your siteFree for contractors, schools, and engineering firms. Copy one snippet; it resizes itself.+
Preview the embed

Please keep the credit line under the calculator. The tool runs entirely in your visitors' browsers; nothing they enter is sent anywhere.

Frequently Asked Questions

What is the Title 24 airflow requirement?+
Under Section 150.0(m)13 of the 2025 Energy Code, ducted cooling systems in single-family homes must deliver at least 350 CFM per ton of nominal cooling capacity. Small-duct high-velocity systems must deliver at least 250 CFM per ton.
What is fan efficacy?+
Fan efficacy is the electrical power the air handler fan draws divided by the airflow it delivers, in watts per CFM. Lower is better. The 2025 limits are 0.45 W/CFM for gas furnace air handlers, 0.58 W/CFM for other air handlers, and 0.62 W/CFM for small-duct high-velocity systems.
Why do high-static systems fail both tests?+
Restrictive ductwork and filters reduce airflow, and a variable-speed blower working against them draws more power to compensate. The same restriction lowers CFM per ton and raises watts per CFM. Measuring external static pressure is the quickest way to find the cause.
Do these limits apply to replacement systems?+
These are the mandatory limits for new systems, which also apply to new systems serving additions. Altered systems have separate criteria in Section 150.2(b)1F. The project's Certificate of Compliance lists which verification applies.