ABS

Title 24 Duct Leakage Calculator

Enter a duct leakage test result and the system's airflow, and see the leakage as a percentage alongside the targets that apply when HVAC equipment or ducts are altered in a California home.

📝 Pre-test check

Use this to see where a system stands before the ECC-Rater visit. The official result is the one the rater records on the Certificate of Verification.

Title 24 Duct Leakage Calculator (single-family, 2025 Energy Code)

How Duct Leakage Is Tested

All registers and grilles are sealed, a calibrated fan is attached to the duct system, and the ducts are pressurized to 25 pascals. The airflow the fan must supply to hold that pressure equals the leakage. For leakage to outside, a blower door pressurizes the house to the same 25 pascals at the same time, so air leaking from the ducts into the house no longer shows up.

When Leakage Is Too High

Most leakage in older systems is at the connections: plenums to equipment, takeoffs to trunks, flex ducts to boots, and boots to drywall. Panned returns and building cavities used as ducts are frequent major leaks. Sealing those points with mastic or listed tape and retesting usually closes most of the gap. When the target still cannot be met, the third route for altered systems is to seal every accessible leak and have it verified by the rater.

Embed this calculator on your siteFree for contractors, schools, and engineering firms. Copy one snippet; it resizes itself.+
Preview the embed

Please keep the credit line under the calculator. The tool runs entirely in your visitors' browsers; nothing they enter is sent anywhere.

Frequently Asked Questions

How is duct leakage percentage calculated for Title 24?+
Leakage percentage = measured duct leakage in CFM ÷ system air handler airflow in CFM × 100. Leakage is measured with a calibrated fan that pressurizes the duct system to 25 pascals with the registers sealed. The airflow it is compared against is determined by the method in Reference Residential Appendix RA3.1.
What is the duct leakage limit for an HVAC changeout in California?+
For altered single-family systems, the California Energy Commission gives three ways to pass: total leakage of 10% or less of system air handler airflow, leakage to outside of 7% or less, or, if neither can be met, sealing all accessible leaks with verification by an ECC-Rater using a visual inspection and smoke test.
What is the difference between total leakage and leakage to outside?+
Total leakage counts all air escaping the ducts, including leaks into conditioned space where the energy is not entirely lost. Leakage to outside counts only leaks to unconditioned areas such as attics and crawlspaces. It is measured by pressurizing the house to the same pressure as the ducts with a blower door, so leaks into the house stop registering.
Why is the 400 CFM per ton value the default?+
400 CFM per ton of cooling has long been the conventional nominal airflow used to express duct leakage as a percentage when system airflow is not measured. Reference Appendix RA3.1 sets the method a rater must use for the project, so enter measured airflow directly if you have it.

Related Title 24 Guides