7 min read · Updated
Acceptance Test Technician (ATT): California's Certification Program
For most of the Energy Code's history, anyone could sign an acceptance test form. Studies found many tests were never performed or performed poorly, so California built a certification program around them. Today, only a certified Acceptance Test Technician may perform the Energy Code's mechanical and lighting controls acceptance tests. This guide explains how the program is structured and how to confirm a technician is qualified.
📝 Educational reference
Three Roles
- Acceptance Test Technician (ATT). The individual who performs the tests. Certified separately for lighting controls or mechanical systems.
- Acceptance Test Employer (ATE). The company that employs ATTs. Every ATT must work for a certified ATE, even if self-employed. The employer cannot perform tests itself.
- Acceptance Test Technician Certification Provider (ATTCP). An organization approved by the California Energy Commission to train, certify, and oversee technicians and their employers.
Approved Mechanical Certification Providers
The Energy Commission's 2025 Energy Code materials list three ATTCPs for mechanical systems. Each publishes a directory of the technicians it has certified:
| Provider | Full name | Technician directory |
|---|---|---|
| NEMIC | National Energy Management Institute Committee (also referred to as TABB) | Find a technician |
| CSPTC | California State Pipe Trades Council | Find a technician |
| RSES | Refrigeration Service Engineers Society | Find a technician |
Lighting controls technicians are certified by CALCTP (California Advanced Lighting Controls Training Program) and NLCAA (National Lighting Contractors Association of America). Check the Energy Commission's ATTCP page for the current list, since approvals are renewed for each code cycle.
What ATTs Are Allowed to Do
A mechanical ATT performs the tests on Certificates of Acceptance numbered NRCA-MCH, covering outdoor air, economizers, demand control ventilation, variable flow fans and pumps, fault detection, and related controls. The full list is in Title 24 Mechanical Acceptance Tests.
Acceptance testing for building envelope and covered processes, such as kitchen exhaust and laboratory fume hoods, does not require an ATT. Those tests may be performed by the builder, contractor, engineer, or commissioning agent.
How Certificates Are Recorded
The ATT completes each Certificate of Acceptance through the certification provider's system. The provider records it and marks it with its logo and a watermark. That mark is what tells a building inspector the certificate is genuine. Providers also run quality assurance programs, including review of a sample of submitted forms and shadow audits of technicians in the field.
How to Verify a Technician
- Ask for the technician's name, certification number, and certifying provider.
- Search for the technician in that provider's directory, linked above.
- Confirm the certification is for mechanical systems and is current.
- Confirm the employer is listed as a certified Acceptance Test Employer.
- When certificates are delivered, check for the provider's logo and watermark.
Building inspectors are advised by the Energy Commission to do the same checks at final inspection, so a certificate from an uncertified technician is likely to be rejected and the test repeated.
Why the Program Exists
The Energy Commission notes that compliance with acceptance testing has been low, often because the required tests were never identified on the Certificate of Compliance, so no one completed them after installation. Certification addresses the quality side of the problem. The rest depends on project teams reading their compliance documents early and scheduling the tests before final inspection.
Sources
- Acceptance Test Technician Certification Provider Program, California Energy Commission
- 2025 Acceptance Testing counter sheet and 2025 Building Inspector's Field Sheet, California Energy Commission